# Open CT Secondary: Why It’s Dangerous and What Not to Do

_Published: 2026-11-17_

Table of Contents

Toggle

- What Is an Open CT Secondary?
- Why an Open CT Secondary Is Dangerous
- How High Can the CT Secondary Voltage Get?
- Current Transformer vs. Voltage Transformer: Why the Rules Differ
- CT Shorting Blocks and Electrical Safety
- Where Open CT Secondary Faults Matter Most
- Open CT Secondary FAQs
- Custom PCB Assembly for Metering and Protection Electronics

**An open CT secondary is dangerous because a conventional current transformer can develop high-voltage spikes across its secondary terminals while current still flows in the primary conductor.** The meter may read zero, but the disconnected wires may still present a shock or arcing hazard. Never open a conventional current-output CT secondary while primary current can flow.

If you suspect an open secondary in service, stay clear of the terminals and notify the qualified electrical personnel responsible for the equipment. Do not probe the gap, reconnect the leads, or attempt to short the exposed terminals yourself. This guide explains the hazard; it is not a switching or maintenance procedure. [Schneider Electric’s CT safety guidance](https://www.se.com/us/en/faqs/FA125574/)

![Window-type current transformer with a circular opening and two secondary terminals](https://www.bestpcbs.com/blog/wp-content/uploads/2026/11/open-ct-secondary-hero.jpg)A window-type current transformer: the primary conductor passes through the opening, while the two secondary terminals connect to the measurement circuit.

## What Is an Open CT Secondary?

An open CT secondary is a break in the loop between the current transformer’s secondary winding and its load. The load, called the **burden**, includes the meter or protection relay input and the resistance of the connecting leads. A lifted wire, loose terminal, or disconnected meter can break that loop without interrupting the primary current.

Picture a feeder with a CT wired to a panel meter. Turning off the display or removing the meter does not necessarily stop current in the feeder. If the meter was part of the only closed secondary path, its removal can leave the CT open even though the rest of the panel appears to operate normally. Here, “open CT circuit” means the _current transformer’s secondary_, not an open trace on a circuit board. For the wider terminology, see the [guide to secondary circuits](https://www.bestpcbs.com/blog/2026/07/secondary-circuit/).

![Closed CT secondary burden loop compared with an open secondary while primary current continues](https://www.bestpcbs.com/blog/wp-content/uploads/2026/11/ct-secondary-paths.jpg)The primary circuit can remain energized in either case. The right-hand gap is in the secondary loop, not the primary.

## Why an Open CT Secondary Is Dangerous

With the burden connected, secondary current produces a magnetic effect opposing that of the primary current. Open the secondary loop and that opposing current largely disappears. More of the primary ampere-turns then magnetize the core, driving it into a nonlinear region where the flux can reverse sharply during each AC cycle.

Faraday’s law gives the key relationship: the magnitude of induced voltage is the number of secondary turns multiplied by the rate of change of core flux. It is the **rapid change in flux**, not the flux magnitude alone, that produces the narrow voltage peaks. In an open circuit, the approximation that the CT delivers its normal rated current into an ever-larger resistance no longer applies. The result is not infinite voltage, but it can still be dangerous. [U.S. NRC open-secondary test report, NUREG/CR-7228](https://www.govinfo.gov/content/pkg/GOVPUB-Y3_N88-PURL-gpo81596/pdf/GOVPUB-Y3_N88-PURL-gpo81596.pdf)

**Hazard**
**What can happen**
**What does not rule it out**

Electric shock
Contact with a terminal or disconnected lead can expose a person to dangerous voltage.
A blank meter display or a zero current reading.

Insulation failure and arcing
Voltage peaks can break down insulation and cause arcing at wiring or terminals. An arc can damage equipment and create a burn or fire hazard.
No visible arc, or an apparently low voltage reading that misses the peaks.

Core heating or loss of accuracy
Abnormal excitation can cause heating, and residual magnetization can affect accuracy after the loop is restored.
A cool enclosure or a meter that starts reading again.

Loss of measurement or protection
A meter or relay may stop receiving a valid current signal even though the feeder still carries current.
A feeder that continues to power its loads.

Overheating is a possible consequence, not a reliable warning. In some U.S. Nuclear Regulatory Commission (NRC) tests, secondary peaks exceeded 6 kV during tests lasting 5 or 10 minutes without a significant observed temperature change. Those are laboratory observations on specific CTs, not a rating or a safe exposure limit. [NUREG/CR-7228, Section 5](https://www.govinfo.gov/content/pkg/GOVPUB-Y3_N88-PURL-gpo81596/pdf/GOVPUB-Y3_N88-PURL-gpo81596.pdf)

![Illustrative secondary voltage waveform with narrow positive and negative peaks](https://www.bestpcbs.com/blog/wp-content/uploads/2026/11/ct-secondary-voltage-peaks.jpg)Conceptual waveform, not measured data and not to scale. The short peaks are the hazard an ordinary reading can miss.

## How High Can the CT Secondary Voltage Get?

There is no single open-circuit voltage for all CTs. In NRC test AM2CT21, a 2,000:5 window-type CT tested at 60 Hz produced secondary spikes of approximately **3.7 kV peak** under the report’s specified test conditions. That is a measured peak for one test, not a normal operating voltage or a prediction for another CT. [NUREG/CR-7228, Table 4-1](https://www.govinfo.gov/content/pkg/GOVPUB-Y3_N88-PURL-gpo81596/pdf/GOVPUB-Y3_N88-PURL-gpo81596.pdf)

For contrast, take a separate **calculated example under normal loaded conditions**: a 5 A RMS secondary driving a purely resistive external burden of 0.10 Ω develops approximately 0.50 V RMS across that burden and dissipates 2.5 W in it. That calculation uses a closed loop. It does not tell you what voltage appears if the loop opens. The ratio on the nameplate, such as 400:5 A, is a current rating, not a voltage limit. Do not intentionally open a live CT to measure the peak.

## Current Transformer vs. Voltage Transformer: Why the Rules Differ

Identify the device by model number, output type and wiring diagram before applying any rule. A conventional CT and a voltage transformer (VT, also called a PT) measure different quantities, and the secondary conditions they are designed to tolerate are different.

**Device**
**Normal output or connection**
**Safety distinction**

Conventional current-output CT
Often rated 1 A or 5 A at rated primary current; connected to an approved low-impedance burden.
An open secondary with primary current present is hazardous. Follow the manufacturer’s instructions for the designated shorting arrangement.

Voltage-output CT with an internal burden
Some models are specified for 333 mV at rated primary current.
Some manufacturers permit their specified output leads to be disconnected because the burden remains inside. Confirm this for the exact model; a similar shape is not evidence.

Voltage transformer (VT/PT)
Provides a scaled voltage to a high-impedance input.
Do not apply the CT shorting rule: a secondary short can cause excessive current. Unloaded does not mean de-energized.

Beckhoff distinguishes its conventional current-output CTs from specified low-power voltage-output models. ABB’s combined instrument transformer instructions likewise distinguish CT secondary shorting from the prohibition on shorting VT secondaries. [Beckhoff CT output guidance](https://infosys.beckhoff.com/content/1033/sct6xxx/19981916427.html); [ABB instrument transformer instructions](https://library.e.abb.com/public/fc0e8bcf35ff4460acb14c98e196f409/1VAP429501-MB_%20Rev%20B_CVC-110BMVoutdoorcombinationtransformers-IOMM_DGT.pdf).

## CT Shorting Blocks and Electrical Safety

A CT shorting block or a CT-rated shorting test switch provides a closed path on the CT side when a meter or relay is isolated under an approved procedure. The important distinction is whether the designated device maintains that path **before** the instrument path opens. An ordinary terminal block or an unlabeled test switch is not proof that the circuit has a shorting function.

The default for work on exposed parts is to de-energize and follow the site’s approved isolation and lockout/tagout procedure. A qualified person must verify the de-energized condition using appropriate test equipment; an off display or switch position is not verification. For U.S. workplaces covered by the rule, see [OSHA 29 CFR 1910.333, especially paragraph (b)(2)(iv)](https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.333). Use the governing local requirements and the equipment manufacturer’s instructions for the installation. An approved shorting device does not by itself authorize energized work.

## Where Open CT Secondary Faults Matter Most

In a **metering panel**, the CT feeds a meter so operators can track feeder current or energy use. During a planned meter replacement, the equipment owner needs to identify the CT output type and the approved test arrangement from the drawings and device manuals. After qualified personnel return the equipment to service, expected readings under known load help check that the metering circuit works; a lit display alone does not.

In a **protection relay circuit**, the CT provides current information the relay uses to decide whether to trip. A lost phase-current input can affect protection even if the feeder continues running. After an open-secondary incident, restoration means more than recovering a reading: the responsible electrical team should determine what inspection and CT, wiring and relay verification are required. A test applied only at the relay input cannot prove the CT and all upstream wiring are intact.

**Use this drawing-review check before authorizing service:** record the CT model, output rating, connected load, documented shorting or isolation arrangement, and who will verify return to service. For example, if a drawing shows a 400:5 A CT feeding a meter but the test block is unmarked, record “shorting function not verified” and refer the job to the responsible electrical lead. Do not infer the test block’s function from its appearance.

## Open CT Secondary FAQs

### Does a 5 A CT have a maximum secondary voltage of 5 V?

No. The 5 A value is rated secondary current under the specified operating conditions. It does not set the secondary voltage during an open-circuit fault.

### Can the meter read zero while the primary still carries current?

Yes. A broken secondary loop can remove the signal the meter needs to display a reading. That tells you nothing about whether the primary is isolated or the CT terminals are safe to touch.

### Does grounding one secondary terminal prevent an open-secondary hazard?

No. A ground connection does not replace the closed burden path. Hazardous voltage can still develop between secondary terminals. Use the grounding arrangement specified for the equipment.

### Are all split-core CTs safe to unplug?

No. “Split-core” describes the mechanical construction, not the output type or fault protection. Check the exact model and its instructions rather than assuming it has an internal burden.

### Can I use an ordinary multimeter to prove a suspected open CT is safe?

No. Narrow peaks may not register correctly on an ordinary meter, and approaching the terminals may expose you to the hazard. Leave verification to qualified personnel following the approved procedure.

### Does closing the circuit again prove the CT was not damaged?

No. A restored reading does not rule out insulation damage, residual magnetization, or loss of accuracy. The equipment owner should have qualified personnel determine what checks are required before returning it to service.

### What should I report if I suspect the secondary opened during service?

From a safe position, report the equipment ID, affected meter or relay, time of the event and any alarms or reading changes. Do not manipulate terminals to gather more information.

### Does a successful relay secondary-injection test clear the CT?

No. An injection test verifies the portion of the circuit reached from the injection point. If the test bypasses the field wiring and the CT, it cannot verify either one.

## Custom PCB Assembly for Metering and Protection Electronics

If you are building the electronics for a metering or protection product, send EBest Circuit your Gerber or ODB++ files, BOM and required assembly test criteria. [Request a PCB fabrication or assembly quote](mailto:sales@bestpcbs.com) and tell us which test results you need with the build. This service covers PCB and PCBA manufacturing, not switchgear servicing or field CT testing.